TH 210-R Humidity and Temperature Transmitter

TH 210 R Humidity Transmitter by KimoKimo’s TH 210-R humidity and temperature transmitter measures humidity and temperature including 0 to 100 % RH and -20 to +80°C (ambient model), -20 to +80°C (pc remote probe), and -40 to +180°C (stainless steel remote probe).

 Featuring:

  • Power supply 24 Vdc/Vac or 100 240 Vac with galvanic insulation
  • "1/4 turn" system mounting with wall-mount plate
  • Calculated parameters absolute humidity, dew point, combination ratio, wet temperature and enthalpy
  • Trend indicator
  • Stainless steel or polycarbonate probe
  • Two 4-wire analogue output 0-5/10V or 0/4-20 mA
  • ABS VO IP65 housing, with or without display
  • 2 relay outputs

TH 210R Humidity Transmitter options

 

  Parameter
 Accuracy (3)
Measuring Range
Resolution
 Relative humidity (% RH)
 Accuracy (Repeatability, linearity, hysteresis):
 ±1.5% RH (from 5 to 95% RH and from 15 °C to 25 °C) Temperature  dependence: ±0.04 x (T-20)% RH (if T<15 °C or T>25 °C)
 From 0 to 100 %RH
 0.1%RH
 Wet temperature(2) (°Ctw, °Ftw)
 Response time: < 10 seconds (from 10 to 80% RH, Vair = 2 m/s)
 From -50 to 100°Ctw
 0.1°Ctw;0.1°Ftw
 Dew-point(2) (°Ctd, °Ftd)
 Response time: < 10 seconds (from 10 to 80% RH, Vair = 2 m/s)
 From -50 to 100°Ctd
 0.1°Ctd; 0.1°Ftd
 Absolute humidity(2) (g/m3 )
 Response time: < 10 seconds (from 10 to 80% RH, Vair = 2 m/s)
 From 0 to 600 g/m3
 0.1 g/m3
 Enthalpy(2) (kJ/kg)
 Response time: < 10 seconds (from 10 to 80% RH, Vair = 2 m/s)
 From 0 to 15 000 kJ/kg
From 0 to 10 000: 0.1 kJ/kg
From 10,000 to 15,000: 1 kJ/kg 
 Combination ratio(2) (g/kg)
 Response time: < 10 seconds (from 10 to 80% RH, Vair = 2 m/s)
 From 0 to 9999.9 g/kg
 0.1 g/kg
 Pt100 temperature
 ±0.3% of reading ±0.25 °C
 Response time: T90 = 0.9 second for Vair = 1 m/s
 Ambient model: from -20 to +80 °C
Remote model with polycarbonate probe: from -20 to +80 °C
Remote model with stainless steel probe: from -40 to +180 °C
 0.1 °C ; 0.1 °F

 

 

Class 210 transmitters have two analogue outputs that correspond to both displayed parameters. It is possible to activate one or two outputs and to select for each between humidity, temperature and the calculated parameters (the default configuration for output 1 is 0-100% RH and 0-50 °C for output 2)

(1)Available only with the remote probe / (2)Calculated value / (3)All the accuracy indicated in this technical datasheet were stated in laboratory conditions, and can be guaranteed for measurements carried out in the same conditions, or carried out with calibration compensation.